Mysterious Loss in TEV Performance
Every now and then someone comes across a problem the details
of which are worth archiving, usually with the intention that it
could or should be used for training purposes. Component manufactures
will often do this, some will turn the experience into a set of
generic instructions that are intended to help future component
appliers avoid similar problems, others will record a description
of the particular scenario as experienced in detail from beginning
to end. It's the detailed scenarios that I always find most interesting.
This article is a representation of one such ,classical, detailed
scenario.
Figure 1
System description
The troublesome system was apparantly a small 1.18kW R12 ice-cream
maker consisting of a freezer mixing section and a storage section,
the storage section is called a conserver, both sections were fed
from one common air cooled hermetic condensing unit and each section
had it's own thermal expansion valve (TEV). The conserver system
ran continuously cycling the condensing unit on temperature control.
The freezer system would then be brought into operation when serving
was required and this of course was done by energizing the liquid
line solenoid valve (LLSV). The component configuration was as per
Figure 1.
Trouble Symptoms
While the conserver section ran continuously without a hitch, the
freezer mixing section consistently showed signs of obvious performance
loss and this was always toward the end of the freezing cycle. Each
time the freezer mixer started there was indeed the required rapid
freezing of the product, however, just as the ice-cream hardness
approached serving quality there was the said sudden loss in freezer
evaporator performance causing the walls to in fact begin thawing
and the ice-cream to quickly re-soften rendering the product unsuitable
for serving.
Initial Speculations
Some areas a technician might be expected to examine first for
symptom cause could be:
- The freezer branch of the 'T' junction situated down stream
of the liquid line filter drier, could there be a restriction
there?
- The mechanical suitability or integrity of the LLSV. Is the
valve pilot operated or direct acting, if pilot operated does
it have sufficient end-of-cycle flow induced pressure drop to
function correctly and not restrict refrigerant flow?
- The refrigerant charge quantity, would more refrigerant be required?
Or would more refrigerant merely flood the condenser during pull
down causing excessive head pressures to delay pull down?
- Is there perhaps end-of-cycle preferential feeding of liquid
refrigerant to the conserver circuit?
- Is it possible that the increased evaporator temperature difference
(TD) in the conserver section toward the freezer sections cycle-end
is robbing compressor capacity.
- Would the addition of a refrigerant receiver help?
- Someone might even have thought the ice-cream's molecular structure
altered with temperature possessed by some sort of thermo-molecular
properties hysteresis. Just kidding.
Diagnostics Procedure
Often, to aid system diagnostics, system modifications of a temporary
or even a permanent nature have to be applied. These modifications
would be to either provide for visuals such as sight glasses or
indirect visuals such as pressure gauges. In this particular case
the foremost question to be asked would be "At end-of-cycle, is
there a solid column of liquid ahead of the freezer section's TEV
and is it at the requisite pressure?". A combination of liquid line
pressure and surface temperature readings at the condensing unit
might indicate all is good but the better technician would insist
on knowing what these readings are immediately before the offending
TEV which would of course require the addition of a pressure tapping
there. Otherwise, the circumstances might suggest that a sight glass
be installed instead. Which option to use might be a subjective
decision. Before deciding, the technician tending this problem might
consider a few principles:
- At the end of a cooling cycle there is more refrigerant in the
evaporator and of course this means less refrigerant in the condenser
or liquid line available to be subcooled. The freezer evaporator
being bottom fed would permit some liquid trapping there during
the expected reduced end-of-cycle refrigerant velocities.
- Since too the end-of-cycle condenser TD would have diminished
so would, further, the degree of available subcool.
- If, ordinarily, without overcharge, this system's design dictates
end-of-cycle liquid subcool values of say 1K to 3K then the accuracy
of a technicians instruments could leave too much room for doubt.
Even with the most accurate instruments available, reading a 1K
or even 2K subcool, there is no guarantee of a vapour-free liquid
column available ahead of the TEV. It is quite normal to witness
vaporous liquid flow coinciding with subcool readings of 1K and
2K.
Figure 2
Re-considering The Initial Speculations
- The flow pressure drop through the 'T' junction, situated down
stream of the liquid line filter drier, would reduce as the square
of the refrigerant velocity and with low load mass flow reductions
would likely reduce more so than any coinciding subcool loss.
- The mechanical suitability of the LLSV could be considered good,
the valve being of the direct acting type. ?
- The refrigerant charge quantity could be verified as sufficient
for end-of-cycle TEV supply by the installation of a sight glass
at position SG1 seen in Figure 2, assuming there are no substantial
pipe frictional or liquid lift related pressure drops.
- Preferential feeding to the conserver section tending to starve
the freezer section could be determined by the installation of
a sight glass in the freezer sections liquid line branch. If the
sight glass is positioned after that lines LLSV at position SG2
as seen in Figure 2 then the technician would only need to decide
whether the offending component was either the 'T' junction or
the LLSV. Certainly, the working parts of the LLSV could be temporarily
removed to eliminate it from this short list of potential causes.
- If the conserver sections TEV superheat setting is adjusted
to increase conserver superheat just as the freezer section reaches
its end-of-cycle run, the conserver can potentially be eliminated
as a cause of overload in respect of compressor capacity, but
then the resulting increase in liquid subcool could falsely remove
the symptom of true cause.
- The addition of a refrigerant receiver shouldn't really be necessary
since the excess refrigerant found on the condenser side of the
system anytime the freezer section solenoid valve is shut should
be comfortably stored in the now proportionately increased condenser
space available since now approximately only half of the condenser
would be needed to handle the reduced heat rejection being brought
from the conserver load on its own.
Diagnosis
As a result of some of the above considerations it was the technicians
decision to install the two sight glasses already mentioned and
shown in Figure 2 namely SG1 and SG2. During the next test run the
technician observed that while SG1 showed a permanence of vapour
free liquid approaching the said 'T' junction, SG2 clearly showed
large volumes of vapour accompanying the liquid supplying the freezer
sections TEV and occurring only near the end of the freezer sections
run cycle coinciding with the drop-off in freezer section evaporator
performance. The sight glass was showing with out doubt that the
freezer sections TEV was not being fed the required solid liquid
column needed for its rated performance. The same observations were
made again but this time with the LLSV's working parts removed except
that it now seemed the end-of-cycle vapour proportions seen in SG2
had increased. It was at this point that the technician speculations
turned toward LLSV's solenoid coil itself. Touching the solenoid
coil and then valve body the technician could feel they were both
unusually warm, much more so than ordinarily expected. The technician
then first partially blocked the condenser air flow to raise liquid
line temperatures which had the expected effect of eliminating the
seen liquid line vapour. This effect was because the temperature
difference between the liquid and valve body had reduced and too
the liquid line velocities had increased meaning there would have
been less heat flow into a greater and more subcooled refrigerant
mass with reduced likelihood of any re-vaporisation. Naturally,
the same improvement was affected when power was cut from the solenoid
coil allowing it and the valve body to cool.
The explanation established as a result of these diagnostics was
that the solenoid valve was of an excessively compact construction
selected to fit the tight space constraints designed into the overall
system and it was this compact design that provided for what we
might consider the efficient transfer of coil heat to the liquid
line and the carried refrigerant.
In summary, the heat produced by this solenoid valve, albeit excessive,
was proportionately sufficient to have the problematic effects due
to the very low refrigerant mass flows associated with the freezer
evaporator system's slight capacity. The freezer evaporator being
bottom fed would tend to trap disproportionately more liquid refrigerant
at low loads as a result of the associated reduced refrigerant velocities.
The effect this trapping had on reduced available liquid line subcool
coupled with the normal end-of-cycle reduced liquid line mass flows
provided the right conditions for this very rare phenomenon to occur.
Solution
A solenoid valve of less compact design was used to replace the
offending solenoid valve and so timely delivery of quality ice-cream
servings were of course finally realised.
|