How to boost your expansion device assembly's
capacity
& overall system energy efficiency
Figure 1
Energy Savings
The expression above, Figure 1, was introduced in the July 2003
publication, to show that overall system power consumption will
be reduced by some 40% of design power consumption in the event
of moderate head pressure reductions, the said savings were expected
when saturated condensing temperature is permitted to drop from
43°C to 23.5°C affected by continued condenser fan operation when
ambient temperatures drop from the summer design of 28°C to the
UK annual average of 10°C. The reduced compressor energy consumption,
against the sustained fan energy consumption, brings about the overall
40% energy savings. However, the primary obstacle to maintaining
system stability during reduced head pressure operation is the subsequent
reduction in expansion device capacity occurring predominantly as
a result of the reduced liquid pressures available ahead of the
device.
TEV Capacity Loss
Then, in last months publication, the TEV capacity change expression
was introduced, Figure 2, predicting TEV capacity change when, for
constant suction side conditions, high side liquid conditions change.
For an R22 system operating with a low side saturated temperature
of 2°C, the high side reduction, mentioned above, brings about a
25% reduction in TEV capacity.
Figure 2
The expression of TEV capacity change predicts that if compressor
capacity is caped at 66% or 75% of full load, during periods of
energy saving reduced head pressure operation, the reduced available
TEV capacity should still cope in the efforts to maintain designed
saturated suction conditions, maintaining almost design evaporator
superheat. A controls philosophy incorporated to achieve this compressor
capacity limiting during low ambients may very well work, especially
if system loads reduce proportionately.
TEV Capacity/Superheat Curves
Figure 3, below, illustrates a theoretical TEV capacity/superheat
curve with dotted lines mapping compressor staging, TEV capacity
and TEV superheat. For constant inlet and outlet pressures and inlet
temperatures the TEV will open or close in response to sensed superheat
through the 2K range of opening superheat, which perhaps could be
called the "proportional band", existing between 2K and 4K of total
superheat. In other words, this theoretical TEV has a static superheat
of 2K, through which the orifice will remain perfectly shut, thereafter
occurs the 2K opening superheat in combination giving the valve
a total operating superheat of 4K. At 25% compressor capacity the
total operating superheat would be 2.5K, 2K static superheat plus
0.5K opening superheat, then at 50% it would be 3K and so forth.
Figure 3
Figure 4, below, illustrates the modified TEV capacity/superheat
curve associated with the energy-saving lowering of saturated condensing
temperatures from the said 43°C to 23.5°C. The illustration shows
that after the full span of 2K opening superheat the valve's modified
capacity is only 75% of design and even the residual capacity, seen
available at slightly higher superheats, would not match the compressors
full load capacity, which we could assume still approximates the
original design capacity of 100kW or more. Without finely set low
side protection, such as LP switches, a new system component balance
establishes at pressures considerably below design. Reduced instantaneous
system power consumption may be witnessed but the increased run
time will generally more than compensate for this, negatively, which
results in an overall reduction in both system capacity and efficiency.
In the case of standard water chillers and DX air conditioning systems,
the resulting misbalance and evaporator starvation means that evaporator
icing is the expected result with or without nuisance LP trips.
Figure 4
Optichiller TEV Supplement
Typically, in response to the above-described TEV troubles, many
engineers opt to use either slightly oversized balanced port expansion
valves or various types of electronic expansion valves. A few years
back I thought of another potential solution, a concept I called
OptiChiller, which is meant to be a simple, inexpensive and an easily
retrofit-able solution. The idea is to supplement TEV capacity with
a fixed orifice system comprising perhaps a ¼" liquid line solenoid
valve and a cut-to-measure capillary tube, sized by trail and error,
to offset the said TEV capacity shortage occurring at 100% compressor
staging.
Figure 5
Figure 5 illustrates how the OptiChiller concept alters the TEV's
superheat/capacity curve bringing total capacity back up inline
with full load compressor capacity, maintaining the original design
total operating superheat. The 4K operating superheat, seen in Figure
5, is being achieved at both 75% and 100% compressor staging. Interestingly,
this TEV capacity supplement could be introduced even during design
summer ambients when, with design liquid pressures, it would reduce
the TEV's operating superheats such that the summer opening superheat
"proportional band" might be caped at approximately 3.5K, increasing
system capacity and efficiency somewhat. Functioning along side
the supplementary fixed orifice expansion device the TEV would adjust
to maintain superheat more stably than would two TEV's competing
in parallel for control of a common suction line superheat.
Liquid Delivery
Like all expansion devices, the OptiChiller concept assumes good
quality liquid is delivered ahead of the combined TEV and OptiChiller
assembly. Proper liquid delivery is in fact probably the most complex
of problems associated with reduced head pressure operation, regardless
of expansion device type. The simplest means to maximise the chances
of good liquid delivery to the TEV inlet is to configure the system
for close coupling, minimizing distances between the condenser or
receiver outlet and the TEV inlet. When close coupling is not possible
then giving the liquid an increased gravity assisted downhill path
to the TEV inlet does help. Where elevations permit, installing
an inline flow-through liquid bulge after the condenser would allow
for seasonal liquid line liquid mass alterations without too much
disruption to available subcool established by liquid head if not
in the condenser.
|