|
Incorrect water chiller piping configuration causing frequent
LP trips
and indirectly causing high space humidity's
I was invited to provide opinion regarding a newly installed air
cooled water chiller system who's twin AHU's were apparently unable
to properly manage the conditioned space's design humidity. It was
also explained that the water chiller itself had been repeatedly
tripping on low pressure safety (LP) since almost the first days
of operation.
The cause turned out to be quite simple, at least more simple
than usual as far as special troubleshooting requests go. It turned
out that the chilled water piping had been reverse connected at
the main return and supply headers, so we had the return water passing
backwards, in a parallel flow configuration, through the chiller's
shell and tube heat-exchanger, then through the chillers local strainer
and on to the supply header. The resulting incorrect strainer position
alone, situated after, rather than before, the heat-exchanger, might
have been sufficient cause for frequent LP trips were there sufficient
unstrained debris to foul the heat-exchanger.
It was also explained to me that as a result of the frequent water
chiller LP trips, in attempt to solve the problem, the manufacturer
had changed the two thermal expansion valve's (TEV's), one for each
compressor. I noticed the replacement TEV's were a well known manufacturer's
anti charge-migration type specially designed to isolate the bulb
from the potentially colder power assembly with the use of a hydraulic-fluid
charged capillary and power assembly. Charge migration from the
TEV's bulb to the power assembly bellows can often occur when the
TEV itself becomes colder than the TEV bulb, this causes lower than
desired power assembly pressures which in turn results in excessive
TEV throttling since the TEV is falsely seeing a reduced superheat.
If I'm permitted an attempt to elaborate on the details of this
scenario, which may yet provide some entertainment.
The dynamics behind the LP trips.
In accordance with logical system component balance laws, subject
to individual component operating characteristics, the minimum operationally
established evaporator temperature difference (TD) is governed by
the TEV's superheat setting. This is to say that even if a systems
evaporator coil and TEV orifice were increased in size to the extent
that the evaporator could satisfy the compressors capacity rating
with a TD lower than the TEV's superheat setting, the TEV would
still throttle refrigerant flow to affect its superheat setting.
Consider that it's the difference in temperature between vapour
leaving the evaporator and saturated liquid near the end of the
evaporator that constitutes superheat. Also, that the highest temperature
the leaving vapour could warm to depends on the warmest medium it
comes into contact with before leaving the evaporator, which is
usually assumed to be the returning cooled medium.
While, ordinarily, heat-exchangers are configured counter-flow
in order that log mean temperature difference (LMTD) be maximized
for most effective use of the heat-exchangers surface area, direct
expansion or dry expansion (DX) evaporators are configured for counter-flow
for a slightly different reason which is simply to maximize the
available TEV superheat. This means that the evaporator dry line,
or otherwise suction line, would be facing, or in contact with,
the warmer returning cooled medium as opposed to the colder leaving
cooled medium.
Perhaps the standard TEV superheat setting for standard water
chilling evaporators is around the 4K mark. If we consider that
often water chilling systems are, either designed to or commissioned
to, run with full load return and supply water temperatures of 10°C
and 5°C over a saturated evaporating temperature of 2°C, it is clear
then that with a counter-flow configuration the maximum available
design superheat would be 8K while with a parallel-flow configuration
the maximum available design superheat would be a mere 3K which
is 1K below our assumed TEV superheat setting of 4K.
A parallel flow configuration wouldn't necessarily have any substantial
effect on the evaporators LMTD because on the refrigerant side of
the heat-exchanger we have a near constant temperature phase-change
fluid. The TEV however, at full load, would be forced to throttle
saturated suction pressure down to a temperature 4K below supply
or leaving water temperature, this in order to affect the TEV's
fully loaded 4K superheat setting, meaning a saturated suction temperature
of 1°C (5°C-4K) would prevail. Further, if the water chiller's leaving
temperature control is programmed to maintain a dead-band of 3K,
meaning water leaving temperatures would fluctuate 1.5K either side
of set-point, then the water chillers leaving temperature would
be dropping to 3.5°C (5°C-1.5K) before a compressor capacity stage
is removed which would permit a temporary saturated suction temperature
of -0.5°C before unloading. This can be expected to occur any time
the compressor unloads from a fully loaded sate to one stage below
fully loaded, which then brings about a welcome saturation suction
pressure rise and too a TEV superheat reduction. The TEV superheat
reduction comes about as the TEV rides down it's Capacity/Superheat
curve. Of course, if the water chiller LP setting is at an equivalent
to a saturated suction temperature of 0°C, as it should be to avoid
a freeze up, then suddenly the likelihood of an LP trip becomes
very real.
The problem with the idea of reducing the TEV's superheat setting
to avoid experiencing sub zero saturated suction temperatures is
that the valve will likely hunt, especially at low loads, continually
over and underfeeding the evaporator, affecting reduced evaporator
efficiency and hence reduced system efficiency. Liquid flood backs
are of course also a common result of low TEV superheat settings
and hunting, which would very likely mean that the frequent LP trips
would simply be replaced instead by frequent compressor oil failure
trips caused by the compressor oil pump being fed a foaming refrigerant
diluted oil. The commissioning engineers had decided in the end
that to raise saturated suction pressures sufficient to avoid the
frequent nuisance LP trips they would raise the water chillers leaving
temperature set point by 2K from 5°C to 7°C. Although this did solve
the LP problems it seemed to have increased the conditioned space's
high humidity problems.
The cause of increased space humidity's.
Originally, extra to the systems frequent LP trips, the conditioned
space's humidity's were occasionally but repeatedly spiking causing
nuisance high relative humidity (RH) alarms. This we guessed was
simply the readmitting of coil condensate back into the supply air
as the chilled water temperature increased to a temperature toward
return air dew point every time the compressors tripped on LP. But
the high RH conditions became a more permanent problem immediately
after the water chiller's nuisance LP trips had been taken care
of. The newer high RH problems were of course a result of the increased
AHU's coil temperatures brought about by the increased water chiller's
set point.
An air conditioning system's total heat load consists of two distinctly
different loads, sensible and latent. The first is merely the cooling
of the air, the second is both the cooling and the condensing of
moisture vapour out from within the air. Sensible heat has to be
removed from the conditioned space at the same rate it is being
introduced to the conditioned space and the same is true of latent
heat. The ratio of the sensible heat to the total heat, sensible
+ latent, is called the Sensible Heat Ratio (SHR).
For any given return air dry and wet bulb temperature the AHU's
SHR is dependant on effective coil temperature, a temperature known
to some as the Apparatus Dew Point (ADP). ADP is always a few degree's
above the temperature of the cooling fluid within the coil tubes
per the temperature gradient that need exist between that fluid
and the cooled medium. ADP is normally about 3K warmer than the
coils contained cooling medium. Once the coil's ADP has dropped
below return air dew point (DP) then for any further drop in ADP
the coils sensible heat ratio reduces while the total coil capacity
increases. Total capacity increases due to increased coil to return
air TD. For a constant ADP an AHU's SHR will increase with increased
dry bulb temperatures and decrease with increased wet bulb temperatures.
Or for a constant dry and wet bulb temperature, an AHU's SHR would
decrease with reduced ADP's. With DX AHU's, reduced ADP's can be
easily achieved by reducing air flow which in turn reduces air to
coil LMTD tending to drop saturated evaporating temperatures affecting
a decrease in SHR for improved moisture removal. But reducing the
air flow over a chilled water fed fan coil doesn't reduce feed water
temperatures, they're controlled by the water chillers set point
and control dead band, only leaving water temperatures are reduced
which has little effect but for a loss in system capacity especially
since the fed water temperatures are already too high.
By my experience, other common causes of increased space humidity's,
or the pre-required increased saturated evaporating temperatures,
have been the likes of increased head pressures, operating parameters
altered by refrigerant retrofits or lost compressor efficiencies
from wear and tear. Increased head pressures causing increased ADP's
and hence increased space humidity's can usually be associated with
fouled condensers, fouled condenser fan blades or slipping condenser
fan belts. With retrofits or drop-in replacements, where say the
TEV's capacity has been increased due to increased pressure drops
and increased net refrigeration effect coinciding with lost compressor
volumetric efficiencies due to increased compression ratios, ADP's
are again caused to rise. If overall system capacity has been increased
by the drop-in then subsequent reductions in compressor run time
will further reduce overall system SHR.
The solution recommended in this particular case was to re-connect
the chilled water piping to the return and supply headers the correct
way round.
Marc O'Brien can be contacted via the Fridgetech.Com Ltd website
at http://fridgetech.com or by mobile phone on 07734 193858.
|